New OptiFlex FWEX driver drv_fwex_107-06-2118 has been posted

Issues Fixed


v107-06-2118

  • Physical input configured in two different MBs as dF and dC shows error.
  • High CPU utilization when ARCNET defined but not connected to another device.
  • Failure during DHCP process stops further DHCP attempts until controller is restarted.
  • Superfluous DHCP discover packets broadcast.
  • Not a Number (NaN) values can be written to BACnet objects.
  • Protection from watchdog timeouts due to prolonged packet floods - FSB_230427.00 - Less Prominent Restart Issue


Enhancements


v107-06-2118

  • Controller requests the existing IP address from DHCP server after lease expiration.
  • Support for new "-A" 1628 & 028 integrated controller models with ARCNET restored.
in News
Automated Logic launches a new 15” equipment touch screen for local control of its PLCs.