v108-08-30000
Models Supported
- G5RE, G5CE, OFHI, OFHI-A, OFISO-E2, OFCSR-E2, OFINT-E2, OFRTR-E2-S2.
Issues fixed in .update files :
- Reading a device object list with more than ~2,900 entries falls back to reading each object in the list individually, causing pending operations to timeout and never complete
- Port S1 packet counts are not updated on hardware without rotary switches
- Controller not responding to non-segmented confirmed requests with broadcast MAC address on local data link
- Digital wire trend in equipment causes control program to halt
- Net LED and Warning Message History in modstat do not display correctly when Ethernet is disconnected on B/SC homed controller
- PCAP files show milliseconds as microseconds
- UDMI payloads have non-string values in quotes
- ARC156 glitch filter set too wide, sometimes leading to discarded bits from distant controllers on longer ARCNETs
- Historian enabled trends with max samples and historian triggers set to 0 send buffer ready notifications with each trend sample, leading to high CPU load
- Driver upgrade/downgrade may result in download errors that require downloading again
- Point count exceeded messages may be erroneously displayed
- Disable Service Ports option may not actually disable service ports when checked
- Network points to devices on BACnet/Ethernet networks that have gone offline never go into error
- Driver > Connections page not displaying when homed on B/SC
- External BACnet property writes are not triggering an archive
- Locked I/O alarm may continue to show after CP with locked point is removed
- Controller homed on B/SC network treating "this" as BACnet object name instead of wildcard
- Changing a MODBUS TCP network point URL or refresh time may cause point to show "20 - No connection available" and stop being serviced until restart
- CPU usage dramatically increases as number of network points increases
- Disabling/Re-enabling a network point causes it to show Uninitialized until restart
- BACnet network points that don't initially bind correctly are never retried
- Who-Has is never sent when using device name in network point
- When the enable input on a BACnet ANO2 MB changes to True the MB always writes a 0 prior to writing the actual wire value
- Network points pointing to internal BACnet objects in Airflow MB show Configuration Error
- Errors are initially shown on BACnet ANOs using object names when points are actually updating correctly
- Network points using wildcards (e.g. */<objectname>) will not bind to points residing in the same controller
- Redownloading a controller with a large number of MODBUS points causes the controller to run out of memory
Enhancements
- Support for OFRTR-E2-S2
- ARCNET Controllers Online now shown in S1/S2 Connection tab of Driver page
- Added option to disable Eth0 and Eth1
- Security improvements
- MAC address can now be changed on the home network, via the BAS Driver page
- Support for Invensys ASD PPD
Known Issues
- See Gen5 Firmware Advisory.